[Inputs]
Input Connection: Pluggaable terminal block for one external channel, excitation controls and alarm outputs
Chanenls: One on-board thermistor temperature (-40°C ~ 70°C,-40°F ~ 158°F)
One external 10VDC channel.
Resolution: 0.0018%
Accuracy: ± 0.05% FSR @ 25°C
Input Impedance: Over 1 MOhms
Overvoltage Protection: up to -3VDC ~ +40VDC
[Alarms]
Channel Alarms: Two editable alarm thresholds
Alarm Output:
ALARM1 & A2/E terminal strips can be configured as alarm outputs
Alarm-On: MOSFET(N-Channel) switch on
Alarm-Off: MOSFET(N-Channel) switch off
Max Power: 200mA @ 24VDC
With purchase of SiteView software, Site-Log can report alarm status to host PC via USB, Modem or Ethernet Device Server.
Alarm-On Delay: programmable 0 - 10 minutes delay with 1-minute increment.
Alarm Indicator: On-board LED lights in red when in alarm condition.
[On-board Memory]
Size: 4 Mega bytes (2MB readings)
Data Retention: Over 20 years
[Sampling]
Sampling Interval: 20 milliseconds to 12 hours user selectable. (external power supply required if interval less than one second)
Logging Mode: Stop recording or FIFO when memory is full
Logging Activation: Programmable instant, start delay or field push button activation.
[Communications]
Interface: USB (Mini-USB-B) (USB-A-mini USB-B Cable included)
AUX(RJ11) for direct TTL level communications
Baud Rate: Auto-detect baud rate from 2400 to 115200 bps on both USB and AUX.
[Battery]
Power: Built-in 3.6V Lithium Battery.
Battery Life: 12 years based on 1 minute sampling interval.
[Software]
SiteView: (Sold separately)
Configuration, downloading, plotting, real-time view, custom calibration and custom equation.
Software Requirements:
Computer with 1.0 GHz or faster processor
256 MB Memory or higher
1.0 GB of available hard-drive space or higher
Windows XP with SP2 or later, Vista, Window 7
At least one USB port or one COM port.
[Physical]
Material: Aluminum enclosure.
Dimension: 88 X 64.2 X 24 mm (3.46 X 2.53 X 0.95 inches).
Weight: 200g
Mounting: Probe/wall-mount holes for hanging/mounting.
[Others]
LED Indicator:
Tri-Color LED: (can be disabled for power saving)
Normal Sampling: green when sampling.
Alarm: red when sampling.
Low Battery: amber when sampling.
Excitation Control:
A2/E terminal strip can be configured as excitation control output for driving the power of connected devices.
Warm-up delay interval settings: 10 to 240 seconds with 10-second increment.
Operating Environment: -40 ~ +70 °C (-40 °F ~ 158 °F), 0 ~ 95% RH non-condensing.
Clock Accuracy: ± 1 mintue per month.
Approvals: CE, FCC
품명 | 상품페이지 참고 |
---|---|
모델명 | 상품페이지 참고 |
법에 의한 인증·허가 등을 받았음을 확인할 수 있는 경우 그에 대한 사항 | 상품페이지 참고 |
제조국 또는 원산지 | 상품페이지 참고 |
제조자 | 상품페이지 참고 |
A/S 책임자와 전화번호 또는 소비자상담 관련 전화번호 | 상품페이지 참고 |
Site View
구매후기가 없습니다.
회사명 ㈜테솔 |
대표 장지훈 |
주소 경기도 용인시 기흥구 흥덕1로 13 흥덕IT밸리 P동 102-A호
사업자 등록번호 129-81-98838 |
전화 031-713-5988 |
팩스 031-713-5983 |
E-mail sales@tessol.com
통신판매업신고번호 제 2014-용인기흥-0097호 |
개인정보 보호책임자 장인석